Enhancing our environment by preserving water resources for future generationsEnvironmental Protection, Inc.CALL EPI at 800-OK-LINERHow to Contact EPI
Enhancing our environment by preserving water resources for future generationsEnhancing our environment by preserving water resources for future generationsEnhancing our environment by preserving water resources for future generations
Enhancing our environment by preserving water resources for future generationsHOMEPRODUCTSSERVICESTechnical InfoThe Liner LetterCase StudiesSearchSite MapFAQ
Enhancing our environment by preserving water resources for future generations

ULC Listed HAZGARD® series of geomembranes


EPI can provide two HAZGARD brand geomembrane materials that are ULC listed for the secondary containment of fuels.
 
IMAGE1 HAZGARD® 500 and 1000 are UL listed in Canada to meet the requirements of ULC/ORD-C58.9 (1997) for gasoline and diesel fuel handling facilities. UL Listed geomembranes are a requirement of the National Fire Code of Canada and are applicable to commercial fuel handling facilities and federal government installations.

HAZGARD® 500 and 1000 are also excellent general secondary containment materials when used for the storage of compatible chemicals. The HZ 1000 is tested as being suitable for the secondary containment of both above ground and below ground tanks. The HZ 500 is suitable for the secondary containment of above ground tanks only. Both materials are suitable for both flammable and combustible liquid containment including oxygenated fuels.

HAZGARD® 500 and 1000 materials are welded to size in our fabrication facility.

 
 
19 Dec 2006 HAZGARD® Minimum Material Properties
Style ASTM (S) HAZGARD® 500(S) HAZGARD® 1000(S)
ULC Listed
Yes; Class 1A Yes; Class 1B
Thickness (Nominal) D1593 38 mil
0.95 mm
27 mil
0.68 mm
Thickness Minimum D1593 36 mil
0.91 mm
26 mil
0.65 mm
Tensile Strength (MD) D751 180 lbs
800 N
400 x 350 lbs
1,775 x 1,555 N
Elongation D751 25 % 25 %
Tear Strength (MD) D751-B
Tongue
22 lbs
98 N
150 lbs
667 N
Low Temperature D2136 -40°F
-40°C
-45°F
-43°C
Flammability ULC Self
Extinguishing
N/A
 
19 Dec 2006 HAZGARD® Minimum Shop Seam Strengths
Style ASTM (S) HAZGARD® 500(S) HAZGARD® 1000(S)
Heat Bonded Seam Strength D6392
25.4 mm
(1") Strip
89 ppi
15.6 N/mm
100 ppi
17.5 N/mm
Heat Bonded Peel Adhesion Strength D6392
25.4 mm
(1") Strip
20 ppi
3.5 N/mm
15 ppi
2.6 N/mm
 
19 Dec 2006 HAZGARD® Minimum Field Seam Strengths
Style ASTM (S) HAZGARD® 500(S) HAZGARD® 1000(S)
Heat Bonded Seam Strength

 

D6392
25.4 mm
(1") Strip

 

70 ppi
12.3 N/mm
80 ppi
14 N/mm
Heat Bonded Peel Adhesion Strength

 

D6392
25.4 mm
(1") Strip

 

20 ppi
3.5 N/mm
15 ppi
2.6 N/mm
 
 
HAZGARD® FABRICATION SIZES
Material
Style
2500 lb Panel
size 1120 kg
4000 lb Panel
size 1800 kg
HAZGARD® 500 8,450 ft2
785 m2
13,500 ft2
1,250 m2
HAZGARD® 1000 13,800 ft2
1,300 m2
22,100 ft2
2,100 m2

Each and every liner panel we produce is a custom panel. The way we set up our shop is unique in that our shop welders produce prefabricated panels to best match your containment area. We size each panel to fit, without waste, in a logical sequence in your containment area. In containments with irregular shapes we size our panels to best accommodate the irregular size.

There are no theoretical limits to the size of the liner panels that we can prefabricate but there are some practical limits, notably panel weight. Panel weight is important because of the limits of handling equipment that will be available in the field. HAZGARD® liners are normally limited to a maximum panel weight of 2,500 lbs (1,200 kg); however, if a skilled installation crew is available then a panel of up to 4,000 lbs (1,800 kg) is possible.

Panels are accordion folded in one direction and then rolled in the other direction. Unfolding instructions and dimensions are marked on the individual liner panel. Each panel is wrapped in an opaque, weather resistant covering suitable for shipment and storage.

All shop fabricated seams are 100% visually inspected by the welding operator. Every panel is tested for Film Tear Bond and destructively tested in peel and shear. Quality control reports are available with each panel produced.

Panels fabricated from HAZGARD® 500 & 1000 materials for secondary containment applications will be identified by a label attached to the panel.

 

 

MAIN LINKS
Installation
Thermal Welding
Durability
Case Studies
Solutions
Quality Control Manual
Published Papers